Pushbutton click timings¶
digitalSTROM pushbutton click timings (H=high, L=low):
Single Click: /- H < 140ms -\ __| |____ Double Click: /- H < 140ms -\ /- H < 140ms -\ __| |__ L < 140ms __| |__ Triple Click: /- H < 140ms -\ /- H < 140ms -\ /- H < 140ms -\ __| |__ L < 140ms __| |__ L < 140ms __| |__ 1xTipp: /- 140ms <= H < 500ms -\ __| |___ 2xTipp: /- 140ms <= H < 500ms -\ /- 140ms <= H < 500ms -\ __| |__ L < 800ms __| |__ 3xTipp: … see above Programming Click (short-long): /- H < 140ms -\ /--------- H >= 500ms ---------\ __| |__ L < 140ms __| |__ Local Programming Click (short-short-long): /- H < 140ms -\ /- H < 140ms -\ /--------- H >= 2500ms ---------\ __| |__ L < 140ms __| |__ L < 140ms __| |__ Hold/Dimming /--------- H >= 500ms ---------\ __| |__